Stock
- Includes a CL601 data logger, batteries, a USB cable, and software on CD
- 0-600 Arms measurement range
- True RMS measurements
- Built-in data logger
- Built-in data memory
- Built-in date and time clock
- Alarm function
- Battery-powered (2 AA cells)
- EN 61010-1; 600V CAT III, 300V CAT IV
Description
True RMS current data logger model CL601 measures 0-600Arms and is powered by 2 AA batteries.
Model CL601 is a member of the Simple logger II series of instruments and is designed for TRMS current measurements. It features an integrated current probe that supports a current measurement range of up to 600A with 0.1A resolution. The instrument features a built in 240,000-sample memory, integrated LED indicators to display status, and a built-in USB interface for uploading configurations and downloading recorded data. The CL601 is powered from two standard AA cells providing complete portability, and a “use anywhere” design.
The CL601’s data logging function supports sample intervals ranging from once every 125 milliseconds (eight times per second) to as long as once every day. Each CL601 measurement is synchronized with the AC line such that 64 samples over one AC line cycle are taken. Frequency tracking is performed over the range of ±2Hz around the nominal line frequency (50 or 60Hz). An integrated real time clock provides time and date stamping of logged current data.
Accessories
Description
NIST traceable calibration certificate for your CL601 Logger. Must be purchased at the same time as the CL601 data logger.
Please Note: This calibration certificate requires a 2 week lead time (adds two weeks to shipping times) and cannot be returned for a refund.
Software
DataView
AEMC Software
Included FREE with your AEMC Logger. Configuration and report generation software.
Specifications
ELECTRICAL | |
Number of Channels: | 1 |
Input: | Split CT – AC Current |
Input Level: | 0 to 600A AC |
Accuracy (50/60Hz): | 0 to 5A: Unspecified 5 to 50A: ±(1% of Reading +1A) 50 to 400A: ±(1% of Reading +0.5A) 400 to 600A for duration <10min: ±(3% of Reading +1A) |
Resolution: | 0.1A |
Maximum Input Current***: | 600A < 1 min |
Sample Rate: | 64 samples/cycle |
Storage Rate: | Programmable from 125ms to 1 day |
Storage Modes: | Start/Stop, FIFO and Extended Recording Mode* (XRM™) |
Recording Length: | 15 minutes to 8 weeks, programmable using DataView® |
Memory: | 240,000 measurement (512kB). Recorded data is stored in non-volatile memory and will be retained even if battery is low or removed. |
Communication: | USB 2.0 optically isolated |
Power Source**: | 2×1.5V AA (LR6) alkaline batteries |
Battery Life: | 100 hours to >45 days (dependent on sample rate/recording length) |
MECHANICAL | |
Dimensions: | 9.25 × 4.0 × 1.63” (235 × 102 × 41mm) |
Weight (with battery): | 17.1 oz (485g) |
Case: | Polycarbonate UL94-V0 |
Jaw Opening: | 1 cable - Ø 1.42” (36mm) 2 cables - Ø 1.00” (25mm) each 2 bus bars - 50 × 5mm |
Vibration: | IEC 68-2-6 (1.5mm 10 to 55Hz) |
Shock: | IEC 68-2-27 (30G) |
Drop: | IEC 68-2-32 (1m) |
ENVIRONMENTAL | |
Operating Temperature: | 14° to 122°F (-10° to 50°C) |
Storage Temperature: | -4° to 140°F (-20° to 60°C) |
Relative Humidity: | up to 85% at 95°F (35°C), Non-condensing |
Altitude: | 2000m |
SAFETY & ELECTRO-MAGNETIC COMPATIBILITY | |
Safety Rating: | EN 61010-2-032; 300V CAT IV, 600V CAT III; Pollution Degree 2 |
Protection Degree: | IP40 |
Electro-Magnetic Compatibility: | EN 61326-1; 07/1997 (+A1 10/1998, +A2 09/2001, +A3 05/2004) |
CE Approved: | Yes |
*This unique recording mode provides the opportunity to continuously record over long periods of time by reducing the storage resolution of the stored data and
maintaining matching resolution for the newest data. Each time the memory fills up using XRM™, every other of the oldest stored samples is discarded making
room for newer samples. This process continues until the recording is manually stopped.
**A memory backup capacitor provides backup power while the batteries are being changed. This backup capacitor will maintain the instrument for up to 10
seconds without batteries installed. After 10 seconds the date and time will need to be reset (data and configuration will be maintained). If the unit is connected to
DataView® via a PC, the battery life is 100 hours regardless of the storage rate.
*** Input level beyond this range may damage the instrument.